Sherwin Williams Firetex M71V2 - Formerly Leighs

SKU
ID4194
UN1263 (Class: 3, Pk Grp: III)
A decorative sheen top coat designed for internal environments over Sherwin Williams intumescent primers.
Available in 5 and 20 Litres
From £95.71 £79.76
In stock
Only %1 left
Product Description

Sherwin Williams Firetex M71 V2 - Formerly Leighs is a decorative sheen top coat designed for internal environments over Sherwin Williams intumescent primers.

Best Uses

Firetex M71V2 provides protection when used in internal semi controlled conditions where condensation may occur. Also used to maintain the appearance of Firetex systems. Ideal for internally dry controlled C1 environments and up to 20 years in an internal semi controlled environment for C2 categories as defined in ISO 12944-2. after drying Firetex M71 V2 can be exposed to weather provided that the specific use or storage does not lead to ponding water due to rainfall, condensation or other site / transportation / storage circumstances.

Application

Ensure all surfaces to be painted are clean, dry and free from all surface contamination. Suitable for application via airless spray, convential spray, brush or roller. Recommended Thinner/Cleaner Sherwin Williams No2. Firetex M71V2 must always be applied to a minimum dry film thickness of 50 microns to provide adequate protection to Firetex single pack intumescent coatings in an internally semi controlled environment where condensation may occur.

IMPORTANT INTUMESCENT PRODUCT NOTE: Always contact Promain’s technical team prior to purchase to obtain a tailored project specification and the advice necessary. The information displayed on this website should only be used as a guide. Promain UK Limited will not be held liable for any resulting damage to property, human life or monetary costs incurred due to incorrect specification, preparation, application or maintenance that has occurred due to negligence by either the purchaser or applicator. This includes your failure to have contacted us to obtain the relevant advice/specification.

Technical Details

Cellulosic Fire Protection of Steel:

  • Specification FP1: Water Based 75µm Site applied for Life of Building (C1), or 50µm for up to 20 years (C2)
  • Specification FP1a: Water Based 75µm Site applied for Life of Building (C1) or 50µm for up to 20 years (C2)
  • Specification FP1b: Water Based 75µm Site applied for Life of Building (C1) or 50µm for up to 20 years (C2)

Approvals

  • Forumated to meet the requirements of EC directive 2004/42/CE
  • ETAG 18-2

Technical Info

  • Do not apply at ambient air temperatures under 5°C
Components: Single Pack
Type: Intumescent Topcoat
Finish: -
Stock Colours: Full range - see web site
Tintable: Yes. Please note, bespoke tints are non refundable / exchangeable
VOC Content: 472 gms/litre
Volume Solids: 44 +/- 2%
Suitable Substrates: Internal galvanised decking (C1 environment only) and Sealed Steelwork
Application Method: Brush, Roller, Airless Spray or Conventional Spray
Theoretical Coverage: 8.8 m2/ltr
Wet Film Thickness (WFT): 114 microns
Dry Film Thickness (DFT): 50 microns
Induction Time: -
Pot Life: -
Touch Dry: 1 hour at 15°C
Overcoatable: 4 hours at 15°C
Fully Cured: -
Cleaner / Thinner: Cleanser / Thinners no.2
Shelf Life: 2 years from date of production unopened or 'use by' date where specified
Packaging: Available in 5 Litres and 20 Litres