£7.75 delivery on orders excluding certain products & postcodes *
International Interchar 1190 is formulated as a single component, borate and chlorine free, water borne intumescent coating designed for on-site application to structural steel requiring protection from cellulosic fire.
Interchar 1190 is a low VOC acrylic intumescent material independently fire tested in accordance with BS 476 Parts 20-22.
All surfaces to be coated should be clean, dry and free from contamination. Prior to paint application, all steel surfaces should be assessed and treated in accordance with ISO 8504:2000. Oil or grease should be removed in accordance with SSPC-SP1 Solvent Cleaning.
Primed Steelwork
Interchar 1190 should always be applied over a recommended anti-corrosive coating scheme. The primer surface should be dry and free from all contamination and Interchar 1190 must be applied within the overcoating intervals specified (consult the Interchar 1190 Application Guidelines). Areas of breakdown, damage etc., should be prepared to the specified standard (e.g. Sa2½ (ISO 8501-1:2007) or SSPC-SP6, Abrasive Blasting, or SSPC-SP11, Power Tool Cleaning) and a full coat of primer applied prior to overcoating with Interchar 1190.
Metallic Zinc Primed Surfaces
Interchar 1190 can be applied over approved epoxy metallic zinc primers, provided that these have been overcoated with an approved tie coat. Ensure that the primed surface is clean, dry and free from contamination prior to application of the Interchar 1190.
Recommended tie coats are International Intergard 269 or International Intergard 276.
IMPORTANT INTUMESCENT PRODUCT NOTE: Always contact Promain’s technical team prior to purchase to obtain a tailored project specification and the advice necessary. The information displayed on this website should only be used as a guide. Promain UK Limited will not be held liable for any resulting damage to property, human life or monetary costs incurred due to incorrect specification, preparation, application or maintenance that has occurred due to negligence by either the purchaser or applicator. This includes your failure to have contacted us to obtain the relevant advice/specification.
The following primers are approved for use with Interchar 1190:
Interchar 1190 may also be applied over Interzinc 52 providing a suitable tie coat is also used; please see product data sheet.
The following topcoats are approved for use with Interchar 1190:
There is a wider range of primers and topcoats which may be suitable for use with Interchar 1190; please contact our technical team for further information and assistance.
Components: | Single Pack |
Type: | Waterborne Intumescent |
Finish: | Matt |
Stock Colours: | White |
Tintable: | No |
VOC Content: | 0 g/L |
Volume Solids: | 69% |
Suitable Substrates: | Interior steel beams |
Application Method: | Airless Spray, Brush, Roller |
Theoretical Coverage: | Consult our technical team for loading tables |
Wet Film Thickness (WFT): | Consult our technical team for loading tables |
Dry Film Thickness (DFT): | Consult our technical team for loading tables |
Induction Time: | - |
Pot Life: | - |
Touch Dry: | 4 hours at 15°C |
Overcoatable: | After 12 hours minimum at 15°C |
Fully Cured: | |
Cleaner / Thinner: | Water |
Shelf Life: | 12 months minimum at 25°C (77°F). Subject to re-inspection thereafter |
Packaging: | Available in 20 Litres |